Commission Delegated Regulation (EU) 2024/1681of 6 March 2024supplementing Regulation (EU) No 305/2011 of the European Parliament and of the Council by establishing classes of performance in relation to the resistance to fire of construction products(Text with EEA relevance)

Den Europæiske UnionForordning2024

European Union

Commission Delegated Regulation (EU) 2024/1681 of 6 March 2024 supplementing Regulation (EU) No 305/2011 of the European Parliament and of the Council by establishing classes of performance in relation to the resistance to fire of construction products (Text with EEA relevance) THE EUROPEAN COMMISSION, Having regard to the Treaty on the Functioning of the European Union, Having regard to Regulation (EU) No 305/2011 of the European Parliament and of the Council of 9 March 2011 laying down harmonised conditions for the marketing of construction products and repealing Council Directive 89/106/EEC OJ L 79, 16.3.2006, p. 27. , and in particular Article 27(1) thereof, Whereas: (1) Commission Decision 2000/367/EC Commission Decision of 3 May 2000 implementing Council Directive 89/106/EEC as regards the classification of the resistance to fire performance of construction products, construction works and parts thereof (OJ L 133, 6.6.2000, p. 26). establishes a system for classifying the performance of construction products with regard to their resistance to fire. That system is based on a harmonised solution for assessing that performance and for classifying the results of those assessments. (2) Decision 2000/367/EC does not cover certain classes of performance and thus limits the possibility to declare a more detailed performance. It is therefore necessary to establish classes of performance that are up-to-date to the latest technological and market developments. (3) New classifications for non-loadbearing elements or products with a fire-separating function applicable to unloaded roofs, non-mechanical fire barriers for ventilation ductwork, penetration seals, combined penetration seals, linear joint seals and air transfer grilles should be added. (4) The obsolete classification R for load-bearing elements with a fire-separating function applicable to floors and roofs should be removed as it is effectively covered with the table related to load-bearing elements without a fire-separating function. (5) The technical progress in the assessment methods also requires more detailed explanations and points of reference as regards the products, including revised information in notes. (6) In order to enable manufacturers to declare sufficiently detailed classes of performance of construction products with regard to their resistance to fire in line with the latest technological and market developments, and in the interest of legal clarity, Decision 2000/367/EC should be repealed. (7) In accordance with Article 27 of Regulation (EU) No 305/2011, classes of performance in relation to the essential characteristics of construction products need to be established by the Commission. In accordance with Article 27(2) of that Regulation, those classes are to be used in harmonised standards, HAS ADOPTED THIS REGULATION:

Article 1

Classes of performance in relation to the resistance to fire of construction products, as set out in the Annex, are established.

Article 2

Decision 2000/367/EC is repealed.

References to Decision 2000/367/EC shall be construed as references to this Regulation.

Article 3

This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the European Union. This Regulation shall be binding in its entirety and directly applicable in all Member States. Done at Brussels, 6 March 2024. For the Commission The President Ursula von der Leyen

Annex

ANNEX A. SYMBOLS For the purposes of this Annex the following symbols apply: RLoad-bearing capacityEIntegrityIInsulationWRadiationMMechanical actionCSelf-closingC0-5Durability of self-closing:Use category (C)Number of cycles5≥ 2000004≥ 1000003≥ 500002≥ 100001≥ 5000≥ 1SSmoke leakage (in context of ventilation systems)/Smoke control (in context of doors)PContinuity of power and signal supply under the standard time temperature curvePHContinuity of power and signal supply under constant temperatureG/OSoot fire resistanceKFire protection abilityTTemperature class expressed in maximum gas temperature in °C (operating temperature)DStability duration under constant temperatureDHStability duration under the standard time-temperature curveFFunctionality of powered smoke and heat ventilatorsBFunctionality of natural smoke and heat ventilators B. CLASSES OF PERFORMANCE IN RELATION TO THE RESISTANCE TO FIRE OF CONSTRUCTION PRODUCTS General The relevant definitions, tests and performance criteria are fully described or referenced in the European resistance to fire classification standards, harmonised European product standards, European testing standards, and relevant parts of Eurocodes. If for asymmetrical elements the declared class of the element is only valid from one side, the class shall be accompanied by this information. The following classes of performance are expressed in minutes unless otherwise specified.

  1. Load-bearing elements without a fire-separating function Table 1 Applies toWalls, floors, raised floors, roofs, beams, columns, balconies, walkways, stairsR152030456090120180240360
  2. Load-bearing elements with a fire-separating function Table 2.1 Applies toWallsRE152030456090120180240360REI152030456090120180240360REI-M152030456090120180240360REW152030456090120180240360 Table 2.2 Applies toFloors, roofs, roof windows, rooflights and shuttersRE152030456090120180240360REI152030456090120180240360C The C classification may be declared where a self-closing device is fitted and the element or product was not manually closed for the purpose of the test. Optionally, for durability of self-closing, the C classification may be complemented by the digits 0 to 5 according to the use category where cycle testing has been carried out. Table 2.3 Applies toRaised floorsRE152030456090120180240360REI152030456090120180240360Notes The classification shall be made specific depending on the exposure. The absence of the designation letter r refers to standard temperature/time curve exposure (full fire resistance) whereas its presence refers to the constant temperature attack of 500 °C (reduced exposure).

Raised floors satisfying the standard temperature/time curve exposure for a given time are considered to satisfy the reduced exposure conditions for at least the same period. 3. Products and systems for protecting load-bearing elements Table 3.1 Applies toCeilings with no independent fire resistanceAssessment of the contribution to the fire resistance of structural members: Expressed in terms of classification of the load-bearing element being protected.NotesIf satisfying the criteria with regard to the semi-natural fire, the symbol sn is added to the classification. Table 3.2 Applies toFire protective coatings (reactive), boards (slabs and mats), renderings (sprays), claddings and screensAssessment of the contribution to the fire resistance of structural members: Expressed in terms of classification of the load-bearing element being protected.NotesFor coatings, if satisfying the criteria with regard to the slow heating curve, the symbol IncSlow is added to the classification. 4. Non-loadbearing elements or products with a fire-separating function Table 4.1 Applies toPartitions (including partitions incorporating uninsulated portions) and fixed windowsE152030456090120180240360EI152030456090120180240360EI-M152030456090120180240360EW152030456090120180240360 Table 4.2 Applies toUnloaded roofsE152030456090120180240360EI152030456090120180240360EW152030456090120180240360 Table 4.3 Applies toCavity barriersE152030456090120180240360EI152030456090120180240360NotesThe classification is completed by a separate indication, if satisfying the sudden exposure test for cavity barriers. Table 4.4 Applies toCeilings with independent fire resistanceEI152030456090120180240360NotesThe classification is completed by indicating how the element has been tested, and refers to a fire from above (a→b) or from below (b→a) or both (a ↔b). Table 4.5 Applies toFacades (curtain walls) and external walls (including glazed elements)E152030456090120180240360EI152030456090120180240360EW152030456090120180240360Notes The classification is completed by (i→o); (o→i); or (i↔o) to indicate whether the element has been tested and fulfils the requirements from the inside only; from the outside only; or from both sides respectively. The addition of the suffix ef indicates that the test was performed on the basis of the external fire curve. Table 4.6 Applies toNon-mechanical fire barriers for ventilation ductworkE152030456090120180240360EI152030456090120180240360Notes In addition to meeting the requirements related to integrity (E), the non-mechanical fire barrier shall also: (a) be tested from both sides, and (b) achieve 360 m3/(m2h) maximum leakage rate with reference to nominal duct cross-sectional area during the fire test. There is no S classification for this product, as it has no ambient temperature smoke performance. ve and/or ho show the product is intended to be used for vertical and/or horizontal use. Table 4.7 Applies toPenetration sealsE152030456090120180240360EI152030456090120180240360Notes

The classification is expressed in terms of classification of the supporting construction with fire-separating function being penetrated. The classification of pipe penetration seals is completed by the addition of U/U, C/U, U/C, or C/C depending on the tested pipe end configuration inside the furnace and outside the furnace respectively (U – uncapped; C – capped). Table 4.8 Applies toCombined penetration sealsE152030456090120180240360EI152030456090120180240360Notes The classification is expressed in terms of classification of the supporting construction with fire-separating function being penetrated. The classification shall be completed with the additional relevant classifications of combined elements as given in this annex. Table 4.9 Applies toLinear joint sealsE152030456090120180240360EI152030456090120180240360Notes The classification is completed by the addition of the symbols H, or V, or T indicating that the classification is valid for the corresponding orientation (Horizontal supporting construction; Vertical supporting construction – vertical joint; Vertical supporting construction – horizontal joint respectively), M, or F, or B indicating the type of splices (Manufactured; Field; or Both manufactured and field respectively), X; or Mxxx indicating the movement capability (No movement; or Movement induced (in %) respectively), including the subscript lat or shear indicating the induced movement, and W w1 to w2 indicating the joint width range (in mm) for which the classification criterion is satisfied (w1 being the lower width and w2 the higher width limit). Table 4.10 Applies toFire resisting doorsets, openable windows (in walls and roofs), openable rooflights and shutters (including those that incorporate glazing, closing devices and other building hardware)E152030456090120180240360EI152030456090120180240360EW152030456090120180240360S200For elements and products having passed smoke control criteria depending on test conditions fulfilled.Sa3 or Sa4For elements and products having passed smoke control criteria depending on test conditions fulfilled.C The C classification may be declared where a self-closing device is fitted and the element or product was not manually closed for the purpose of the test. Optionally, for durability of self-closing, the C classification may be complemented by the digits 0 to 5 according to the use category where cycle testing has been carried out. Notes The EI classification is completed by the addition of the suffix 1 or 2 to indicate which definition of insulation is used. In the case the classification does not cover heating on both the closing and the opening face, this shall be made explicit in the classification. This table does not include or address products for smoke ventilation. Additional smoke control classification of large industrial doorsets is possible to a leakage limit of 50 m3/h. Table 4.11 Applies toClosures for conveyers and track bound transportation systemsE152030456090120180240360EI152030456090120180240360EW152030456090120180240360C

The C classification may be declared where a self-closing device is fitted and the element or product was not manually closed for the purpose of the test. Optionally, for durability of self-closing, the C classification may be complemented by the digits 0 to 5 according to the use category where cycle testing has been carried out. Notes The EI classification is completed by the addition of the suffix 1 or 2 to indicate which definition of insulation is used. An EI classification shall be generated for those cases where the test specimen is a pipe or duct configuration with no assessment of the closure for the conveyor system. Sustained operational capability of any clearing device and/or any separating device for a conveyor system is identified by using a T. Table 4.12 Applies toAir transfer grillesE152030456090120180240360EI152030456090120180240360EW152030456090120180240360Notes If satisfying the criteria with regard to integrity during the open state, the symbol resist flame is added to the classification. If satisfying the criteria with regard to the smoldering curve, the symbol IncSlow is added to the classification. Table 4.13 Applies toService ducts and shaftsE152030456090120180240360EI152030456090120180240360NotesThe classification defines how the element has been tested and refers to a fire from the inside (i→o) or from the outside (o→i) or both (i ↔o). In addition, the symbols ve and/or ho show the product is intended to be used for vertical and/or horizontal use. Table 4.14 Applies toChimneysG + distance in mm (e.g. G 50) or O + distance in mm (e.g. O 50)E152030456090120180240360EI152030456090120180240360T (operating temperature) in °C80100120140160200250300400450600Notes Distance not required for built-in products. The classification defines how the element has been tested and refers to a fire from the outside (o→i) or both (i ↔o). ve and/or ho show the product is intended to be used for vertical and/or horizontal use. Table 4.15 Applies toWall and ceiling coveringsK110152030456090120180240360K210152030456090120180240360NotesThe suffixes 1 and 2 indicate which substrates, fire behaviour criteria and extension rules are used in this classification. 5. Products for use in ventilation systems (excluding smoke and heat exhaust ventilation) Table 5.1 Applies toFire resisting ventilation ductsE152030456090120180240360EI152030456090120180240360S10 m3/(m2h) maximum leakage rate with reference to the duct surface area during the fire test Notes In addition to meeting the requirements related to integrity (E) the duct must also achieve 15 m3/(m2h) maximum leakage rate with reference to duct surface area during the fire test. The classification defines how the element has been tested and refers to a fire from the inside (i→o) or from the outside (o→i) or both (i ↔o). ve and/or ho show the product is intended to be used for vertical and/or horizontal use. The classification shall indicate the pressure difference used in the test. Table 5.2 Applies toFire dampersE152030456090120180240360EI152030456090120180240360S

200 m3/(m2h) maximum leakage rate with reference to nominal duct cross sectional area: (a) smallest size at ambient temperature; (b) largest size at ambient temperature and during the fire test. Notes In addition to meeting the requirements related to integrity (E) the fire damper shall also: (a) be tested from both sides, and (b) achieve 360 m3/(m2h) maximum leakage rate with reference to nominal duct cross sectional area during the fire test. ve and/or ho show the product is intended to be used for vertical (e.g., wall mounted) and/or horizontal (e.g., floor mounted) use. H indicates a fire damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a horizontal blade axis or geometry. V indicates a fire damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a vertical blade axis or geometry. 6. Products to be used within electrical, power control and communication building service installations Table 6.1 Applies toFire protective systems for cable systems and associated componentsP152030456090120180240360Notes The classification shall indicate: The type of cables which can be installed within the fire protective systems, i.e. any standard cable or only specific cables; and the cables configurations which can be protected and the operating voltage, i.e.: either to all types of power cables (rated voltage 300/500 V) for an operating voltage up to 230/400 V (three-phase AC); either to all types of power cables (rated voltage 450/750 V up to 0,6/1 kV) for an operating voltage up to 400/690 V (Three-phase AC); either to all types of signal-/control cables (rated voltage up to 170 V) for an operating voltage up to 110 V; or any combination of the above possibilities. Table 6.2 Applies toUnprotected electric, power control and communication cables with intrinsic fire resistancePca152030456090120180240360NotesFor power cables and control cables the classification shall indicate for which rated voltage the performance criteria are satisfied. Table 6.3 Applies toUnprotected small electric, power control and communication cables with intrinsic fire resistance (< 20 mm diameter and with conductor sizes ≤ 2,5 mm2)PHca152030456090120180240360NotesFor power cables and control cables the classification shall indicate for which rated voltage the performance criteria are satisfied. 7. Products to be used in smoke and heat control systems Table 7.1 Applies toSingle compartment smoke control ductsE600152030456090120180240360S5 m3/(m2h) maximum leakage rate with reference to duct surface area at ambient temperature and 5 m3/(m2h) maximum leakage rate related to the duct surface area during the fire test.Notes In addition to meeting the requirements related to integrity (E) the duct must also achieve 10 m3/(m2h) maximum leakage rate with reference to duct surface area during the fire test. The classification is completed by the suffix single for products intended to be used for single compartment use only.

ve and/or ho show the product is intended to be used for vertical and/or horizontal use, within the compartment. 500, 1000, 1500 show the product is intended to be used up to these values of under-pressure, measured in Pa at ambient temperature. Table 7.2 Applies toMulti-compartment fire resistant smoke control ductsE152030456090120180240360EI152030456090120180240360S5 m3/(m2h) maximum leakage rate with reference to duct surface area at ambient temperature and 5 m3/(m2h) maximum leakage rate related to the duct surface area during the fire test. Notes In addition to meeting the requirements related to integrity (E) the duct must also achieve 10 m3/(m2h) maximum leakage rate with reference to duct surface area during the fire test. The classification is completed by the suffix multi for products intended to be used for multi-compartment use. ve and/or ho show the product is intended to be used for vertical and/or horizontal use. 500, 1000, 1500 show the product is intended to be used up to these values of under-pressure, measured in Pa at ambient temperature. Table 7.3 Applies toSingle compartment smoke control dampersE600152030456090120180240360S 200 m3/(m2h) maximum leakage rate with reference to nominal duct cross sectional area: (a) smallest size at ambient temperature; (b) largest size at ambient temperature and during the fire test. Notes In addition to meeting the requirements related to integrity (E) the single compartment smoke control damper shall also: (a) be tested from both sides, (b) pass a maintenance of opening test, and (c) achieve 360 m3/(m2h) maximum leakage rate with reference to nominal duct cross sectional area during the fire test (1) smallest size at ambient temperature, and (2) largest size at ambient temperature and during the fire test. The classification is completed by the suffix single for products intended for single compartment use. ved, vew, vedw and/or hod, how, hodw show the product is intended to be used for vertical and/or horizontal use, together with mounting in a duct or in a wall/floor or both respectively. H indicates a single compartment smoke control damper capable of satisfying integrity (E) for the classification period having a horizontal blade axis or geometry, V indicates a single compartment smoke control damper capable of satisfying integrity (E) for the classification period having a vertical blade axis or geometry. 500, 1000 and 1500 show that the product is intended to be used up to this value of under-pressure in Pa at ambient temperature. AA denotes for use with applications providing automatic activation, MA denotes for use with applications requiring manual intervention or providing automatic activation. C300, C10000, CMOD or C300(N), C10000(N), CMOD(N) show the product is intended to be used in smoke control only systems, fully controlled smoke control systems and smoke control systems combined with environmental systems or modulating smoke control dampers intended to be used in any system having a controlled or variable position, tested under load, or without load (N), respectively.

HOT 400/30 (High Operational Temperature) indicates that the single compartment smoke control damper has been subjected to an additional test to demonstrate that it has the ability to be opened and closed during a period of 30 minutes of temperatures up to 400 °C. Table 7.4 Applies toMulti-compartment fire resistant smoke control dampersE152030456090120180240360EI152030456090120180240360S 200 m3/(m2h) maximum leakage rate with reference to nominal duct cross sectional area: (a) smallest size at ambient temperature; (b) largest size at ambient temperature and during the fire test. Notes In addition to meeting the requirements related to integrity (E) or integrity and insulation (EI) the multi-compartment fire resistant smoke control damper shall also: (a) be tested from both sides, (b) pass a maintenance of opening test, and (c) achieve 360 m3/(m2h) maximum leakage with reference to nominal duct cross sectional area during the fire test (1) smallest size at ambient temperature, and (2) largest size at ambient temperature and during the fire test. The classification is completed by the suffix multi for products intended for multi-compartment use. ved, vew, vedw and/or hod, how, hodw show the product is intended to be used for vertical and/or horizontal use, together with mounting in a duct or in a wall/floor or both respectively. H indicates a multi-compartment fire resistant smoke control damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a horizontal blade axis or geometry, V indicates a multi-compartment fire resistant smoke control damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a vertical blade axis or geometry. 500, 1000 and 1500 show that the product is intended to be used up to this value of under-pressure in Pa at ambient temperature. AA denotes for use with applications providing automatic activation, MA denotes for use with applications requiring manual intervention or providing automatic activation. C300, C10000, CMOD or C300(N), C10000(N), CMOD(N) show the product is intended to be used in smoke control only systems, fully controlled smoke control systems and smoke control systems combined with environmental systems or modulating smoke control dampers intended to be used in any system having a controlled or variable position, tested under load, or without load (N), respectively. HOT 400/30 (High Operational Temperature) indicates that the multi-compartment fire resistant smoke control damper has been subjected to an additional test to demonstrate that it has the ability to be opened and closed during a period of 30 minutes of temperatures up to 400 °C. Table 7.5 Applies toSmoke barriersD600152030456090120180240360DH152030456090120180240360 Table 7.6 Applies toPowered smoke and heat control ventilators (fans), including connectorsF200152030456090120180240360F300152030456090120180240360F400152030456090120180240360F600152030456090120180240360F842152030456090120180240360

Table 7.7 Applies toNatural smoke and heat exhaust ventilatorsB300152030456090120180240360B600152030456090120180240360Βθ152030456090120180240360Notes Where θ indicates the exposure condition (temperature), higher than 300 °C. These products are designed to open in case of fire and do not have an integrity (E) classification.